Table 5. Electrical Output
120V Models 230V Models
PowerLevels(rated at
nominalinputs)
PW5119 1000: 1000 VA, 670W
PW5119 1500: 1440 VA, 960W
PW5119 2000: 1920 VA, 1400W
PW5119 2400: 2400 VA, 1600W
PW5119 3000: 2880 VA, 2250W
PW5119 1000i: 1000 VA, 670W
PW5119 1500i: 1500 VA, 960W
PW5119 2000i: 2000 VA, 1400W
PW5119 2400i: 2300 VA, 1600W
PW5119 3000i: 3000 VA, 2250W
RegulationOnline -10% to +6% of nominal voltage (-15% to +10% using extended range)
RegulationOn-Battery
(NominalVoltage ±5%)
120V for 110, 120, 127V; 100V for 100V 230V for 220, 230, 240V; 208V for 208V
Voltage Waveform Sine wave; <3% distortion with linear load
OvercurrentProtection Online: Branch-rated or resettable circuit breaker;
On-Battery: Active current limit and short circuit protection
OutputReceptacles 1000-1500 VA: Six 5-15
2000 VA: Six 5-15, Two 5-20
2400-3000 VA: Six 5-15, One 5-30
1000-1500 VA: Six IEC-320
2000-3000 VA: Nine IEC-320
Table 6. Weights and Dimensions
120V Models 230V Models
UPS Dimensions
(WxHxD)
7 x 8.8 x 17.1 inches
(17.8 x 22.3 x 43.4 cm)
UPS Weights 1000 VA: 43 lb (20 kg)
1500 VA: 57 lb (26 kg)
2000 VA: 32 lb (15 kg)
2400 VA: 36 lb (16 kg)
3000 VA: 41 lb (19 kg)
BatteryDimensions
(WxHxD)
7 x 8.8 x 17.1 inches
(17.8 x 22.3 x 43.4 cm)
Battery Weights PW5119 1048BP: 47 lb (21 kg) PW5119 1748BP: 70 lb (32 kg)