Powerware (4080 KVA) 9390 User Manual Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 206
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
Installing Options and Accessories
6-2
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
6.2 Preliminary Wiring Procedure
Perform the following procedure before installing wiring:
1. If not already removed, remove the door. Remove the retaining screw located
inside the door at the bottom hinge pivot point, then lift the door off. Save the
retaining screw for reinstallation of the door.
2. Remove the screws securing the control panel door and swing the door open.
Retain the hardware for later use.
3. Remove the screws securing the top internal safety shield panel. Remove the panel
to gain access to the TB1 and TB2 terminal blocks, X-Slot communication bays,
and the top conduit landing plate (see Drawing 164201535-8 starting on
page A-33). Retain the hardware for later use.
4. If installing interface wiring from the bottom of the cabinet, proceed to Step 5;
otherwise, proceed to Step 6.
5. Remove the screws securing the bottom internal safety shield panel and remove
the panel to gain access to the bottom conduit landing plate.
6. Install wiring from the Hot Sync CAN Bridge Card in accordance with the
instructions listed below:
Parallel system wiring (see paragraph 6.3)
RMP wiring (see paragraph 6.4)
RIM (see paragraph 6.5)
SCM (see paragraph 6.6)
Page view 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 205 206

Comments to this Manuals

No comments