Powerware (4080 KVA) 9390 User Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 206
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
Installing the UPS System
3-5
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
NOTE In the following step the pallet tilts and acts as a ramp once the cabinet is rolled
beyond the the center of the pallet. Be sure to restrain the cabinet as it continues to roll
down the pallet/ramp.
WARNING
Do not stand directly behind the pallet while unloading the cabinet. If unloading instructions
are not closely followed, the cabinet may cause serious injury.
8. Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue
rolling the cabinet down the pallet until the cabinet is clear of the pallet.
9. Roll the cabinet to the final installation location.
10. If installing the cabinet permanently, retain the shipping brackets and hardware;
otherwise, discard or recycle the pallet and rear bracket in a responsible manner.
11. If permanently mounting the system, proceed to Step 15; otherwise, continue to
Step 12.
WARNING
The front anti -tip/shipping bracket must be reinstalled; otherwise, injury and damage to the
UPS may result when removing components d uring service. If the bracket is not reinstalled, the
cabinet may tip and cause serious injury and damage.
12. Sec ure the UPS c abinet in position by lowering the levelin g feet until the c abinet is
not resting on the casters and the cabinet is level.
13. Using the retained hardware, reinstall the front anti-tip/shipping bracket (bracket
with wider base) removed in Step 6 to the front of UPS cabinet with the angle
facing outward and adjusted level with the floor (see Figure 3-1).
14. If installing battery and distribution cabinets, proceed to paragraphs 3.2.2 and
3.2.3; otherwise, proceed to paragraph 3.2.4.
15. Using the retained hardware, reinstall the shipping brackets removed in Step 5 to
the front and rear of the UPS cabinet with the angle facing outward (see
Figure 3-1 and Figure 3-2).
16. Secure the cabinet to the floor with contractor-supplied hardware.
17. If installing battery and distribution cabinets, proceed to paragraphs 3.2.2 and
3.2.3; otherwise, proceed to paragraph 3.2.4.
3.2.2 Battery Cabinet Installation
To install the battery cabinet, refer to the Powerware 9390 Integrated Battery Cabinet
(Models IBC-S and IBC-L) Installation Manual. After the battery cabinet is installed, return
to paragraph 3.2.4 to wire the UPS and battery cabinet.