Installing Options and Accessories
6-6
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
6. Install c onduit between the UPS and RIM. See Appendix A for UPS cabinet and RIM
wiring access information.
7. Install wiring between the UPS and RIM. See Drawing 164201535-8 starting on
page A-33 for Hot Sync CAN Bridge Card and RIM location, terminal location, and
wiring information.
NOTE
120 Vac for the RIM should be supplied from the critical bus by facility planners
or the customer.
8. Install 120 Vac power wiring from the critical bus to the RMP. See Drawing
164201535-8 starting on page A-33 for terminal location and wiring information.
NOTE
Setup of the Hot Sync CAN Bridge Card must be performed by an authorized
Powerware Customer Service Engineer. Contact service to schedule a date.
9. Contact your Powerware service representative for verification and testing of the
RIM and its connections prior to making connections with J1 through J4 (see
Table 6-2 and Drawing 164201535-12).
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
Table 6-2. J1 through J4 Interface Connectors
Status J1 through J4 Description
UPS AVAILABLE
Pins 1 and 12 Contacts are closed when the UPS is offline.
UPS OFFLINE
Pins 3 and 13 Contacts are closed when the UPS is operating in
Normal mode.
BATTERY WEAK
Pins 5 and 14 Contacts are closed when approximately two minutes of
battery time is remaining, before the critical load is lost.
UTILITY FAILURE
Pins 6 and 15 Contacts are closed when Utility Failure is detected.