DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
164201535---2 1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
111504B
Installation Information
A-3
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
1. The UPS equipment operating environment must meet weight requirements shown in
Table A and the size requirements shown on Drawing 164201535---9.
2. The UPS cabinet is palleted separately for shipping.
3. Donottiltcabinetsmorethaná10˚ during handling.
4. Dimensions are in millimeters (inches).
5. Thecabinetcanbeinstalledinline ---up–and–match or standalone configurations.
T
a
b
l
e
A
E
q
u
i
p
m
e
n
t
W
e
i
g
h
t
Table A. Equipment Weight
Com
p
onen
t
/
Mo
d
el
Weight
kg (lb)
C
o
m
p
o
n
e
n
t
/
M
o
d
e
l
Shipping Installed Point Loading
UPS Cabinet/9390---40 kVA, 208V/208V 313 (690) 290 (640) 4 at 72.5 (160)
UPS Cabinet/9390---40 kVA, 480V/480V 271 (618) 258 (568) 4 at 64.5 (142)
UPS Cabinet/ 9390---50 kVA, 208V/208V 313 (690) 290 (640) 4 at 72.5 (160)
UPS Cabinet/ 9390---50 kVA, 480V/480V 271 (618) 258 (568) 4 at 64.5 (142)
UPS Cabinet/9390---60 kVA, 208V/208V 313 (690) 290 (640) 4 at 72.5 (160)
UPS Cabinet/9390---60 kVA, 480V/480V 271 (618) 258 (568) 4 at 64.5 (142)
UPS Cabinet/9390---80 kVA, 208V/208V 313 (690) 290 (640) 4 at 72.5 (160)
UPS Cabinet/9390---80 kVA, 480V/480V 271 (618) 258 (568) 4 at 64.5 (142)
6. The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet 36 inches working space
From Back of Cabinet None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet None Required