Powerware (4080 KVA) 9390 User Manual Page 157

  • Download
  • Add to my manuals
  • Print
  • Page
    / 206
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 156
UPS SYSTEM ONELINE DRAWING
093004
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
B
TYPICALPARALLELSYSTEM
(2+1 AND 3+0 CONFIGURATIONS)
4of5
164201535---4
NOTE: 1. UPM and system bypass input feeds
must come from the same source.
2. Remove jumper for dual feed.
3. If the load requires a neutral, a bypass
neutral feeder must be supplied.
OUTPUT TO
CRITICAL LOAD
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 1
E1
E2
E3
E6E
7E8
E12
A
B
SEENOTE2
D
MOB 1
F
E
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 2
E1
E2
E3
E6E
7E8
E12
A
B
SEENOTE2
D
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 3
E1
E2
E3
E6E
7E8
E12
A
B
SEENOTE2
D
MOB 3
MOB 2
MIS
MBP
**
****
CC
C
G
MODULE TIE
CABINET
(OPTIONAL)
Installation Information
A-9
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
A-- AC Input to UPS Rectifier (dual feed)
B-- AC Input to UPS Rectifier (single feed) and Bypass (single and dual feed)
C-- DC Input from Battery
D-- UPM AC Output to Parallel Tie Point
E-- AC Input Source
F-- System Bypass Input
G-- Output to Critical Load
*-- Overcurrent Protection Provided by Others