UPS Installation Plan and Unpacking
2-2
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
2.2.1 Environmental Considerations
The life of the UPS system is adversely affected if the installation does not meet the
following guidelines:
The system must be in stalled on a level floor suitable for computer or electronic
equipment.
The system must be installed in a temperature and humidity controlled indoor area free
of conductive contaminants.
Failure to follow guidelines may void your warranty.
2.2.2 Preparing for Wiring the UPS System
For external wiring requirements, including the minimum AWG size of external wiring, see
Table E through Table H starting on page A-11. The power wiring connections for this
equipment are rated at 9C. If wire is run in an ambient temperature greater than 30°C,
higher temperature wire and/or larger size wire may be necessary. Control wiring for
Emergency Power-Off (EPO) and optional accessories (such as building alarms and
monitoring interface) should be connected at the customer interface terminal blocks
located inside the UPS.
LAN and telephone drops, for use with X-Slot connectivity cards, must be supplied by
facility planners or the customer.
2.3 Inspecting and Unpacking the UPS Cabinet
The next step is inspecting and unpacking the UPS cabinet. The cabinet is shipped bolted
to a wooden pallet and protected with outer protective packaging material (see
Figure 2-1).