Powerware 9315s User Manual Page 165

  • Download
  • Add to my manuals
  • Print
  • Page
    / 205
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 164
A---9
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
3
4
DESCRIPTION:
DRAWING NO: SHEET:
164201373---2
TYPICAL PARALLEL CAPACITY/
REDUNDANT SYSTEM WITH SSBM
COMMON BATTERY SYSTEM
2of2
1
1
1
1
2
5
5
NOTE: 1. Accommodates one to eight UPMs. Four
UPM system shown.
2. The input transformer cabinet may be
installed on either the left or the right
side of the UPM cabinet.
3. Refer to the Powerware 9315 UPS
Installation manual provided with the
UPMs, for UPM, battery, and optional
input transformer installation information.
4. Actual SSBM physical arrangement and
cable connection locations may differ
from that shown. See drawings
164201373---11 and 164201373 ---12
for details.
1
3
4
UTILITY POWER INPUT TO UPM
SSBM OUTPUT TO CRITICAL LOAD
UTILITY POWER INPUT TO BYPASS BUS
5
POWERNET DUAL REDUNDANT NETWORK
SSBM INTERFACE -- TERMINAL BLOCK TB1
UPM INTERFACE -- TERMINAL BLOCK TB1
2
UPM OUTPUT TO SSBM INPUT
FOR 9315 --625/750 UPM ONLY:
ALSO INCLUDES DUAL REDUNDANT
NETWORK POWER SUPPLY
SBM INTERFACE -- TB7
UPM INTERFACE -- CANA & CANB
*See Table O of Appendix A for UPM
Output Conductor Sizing.