DESCRIPTION:
DRAWING NO:
5of6
INSTALLATION NOTES
SHEET:
164201373---1
A --- 6
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A 092402
12. The 100% rated bypass input overcurrent protection and bypass input disconnect switch
are to be provided by the user. Table E lists the maximum rating for output circuit breakers
satisfying the criteria for both. Rating is based on 100% of output current for a 100%
breaker.
Table E. Maximum Bypass Input Circuit Breaker Ratings
SSBM Model
owerware 9315
w
tc
oar
ystem
ypass mo
u
e
2500 3000 4000
SSBM Bypass 2500 3000 4000
SMB Bypass 2500 3000 4000
13. The breakers CBS, CBP, FBP, MBP (optional) and MIS (optional) have AT trip ratings and a
maximum Amp Interrupting Capability (KAIC) as shown in Table F.
Table F. SSBM Breaker Trip Ratings and Amp Interrupting Capability
SSBM Model
Powerware 9315 Switchboard System Bypass
2500 3000 4000 All Models
mo
u
e
Trip Rating KAIC
N/A 3000 4000 65
an
2500 3000 4000 100
14. The 100% rated output overcurrent protection and output disconnect switch are to be
provided by the user. Table G lists the maximum rating for output circuit breakers
satisfying the criteria for both. Rating is based on 100% of output current for a 100%
breaker.
Table G. Maximum Output Circuit Breaker Rating s
SSBM Model
owerware 9315
w
tc
oar
ystem
ypass mo
u
e
2500 3000 4000
SSBM 2500 3000 4000
SMB 2500 3000 4000
15. In the Parallel Capacity/Redundant System, each UPS module, Switchboard System
Bypass Module (SSBM), SSBM breakers, and optional equipment are crated separately
for shipping.
16. Donottiltcabinetsmorethan¦10˚during handling.
17. Dimensions are in millimeters (inches).