Powerware 5115 RM User Manual Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
Specifications
44
Powerware
®
5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Table 5. Electrical Output
120V Models 230V Models
Power Levels (rated at
nominal inputs)
500 VA, 320W
750 VA, 520W
1000 VA, 670W
1440 VA, 1000W
500 VA, 320W
750 VA, 520W
1000 VA, 670W
1500 VA, 1000W
Power Factor 500 VA, 0.64
750–1500 VA, 0.67–0.69
Regulation (Normal mode) -10% to +6% of nominal voltage
Regulation (Battery mode),
Nominal Voltage ±5%
Same as selected nominal input voltage
110V, 120V
Same as selected nominal input voltage
220V, 230V, 240V
Voltage Waveform Sine wave
Overcurrent Protection Inverter saturation current limited
Output Receptacles (4) 5-15 (4) 10A, IEC-320
Table 6. Environmental and Safety
120V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 55°C (5°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Audible Noise Less than 45 dBA typical
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)
Safety Conformance UL 1778; UL 497A;
CSA C22.2, No. 107.1
UL 1778, UL 497A (data line only);
CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
Safety Markings UL, cUL UL, cUL, CE, TÜV
EMC (Class B) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003
Page view 49