UPS Communications Interface Port
In addition to configuring the UPS for specific communication options,
you must also ensure proper use of the serial port when connecting the
UPS to your network or monitoring equipment.
CAUTION
The serialport LANcontactsare transistorsand are ratedat a maximumcurrent of
50 mA and a maximumof +40 Vdc.Do notexceedthese ratings orapplyany
negative voltageor ACvoltageto these contacts;otherwise,damage mayoccur to
yourUPS.
Use only the pins specified for your communications configuration. The
use of any additional pins for any of the following interfaces can cause
interference with system communications.
Even though your network uses the specified signal lines, the pins
assigned to these signals at the network end of the cable may vary with
those of the UPS serial port. The connector body and style may vary as
well.
NOTE Standard,pin-for-pincablesmaynot workcorrectly.Consultyour network
softwareor server manualsfor system shutdown pin assignments.
The UPS serial port complies with EIA RS-232 standards. RS-232
specifies a maximum cable length of 50 ft (15m). See Figure 16 for the
location of the serial port.