Powerware 9 User Manual Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 70
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
Installation
30
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
2. Place the battery cabinets underneath or beside the UPS as
showninFigure3.
NOTE Forstacked cabinets,do not placemore than threebattery cabinetsin one
stack.The UPS cabinet must beplacedon top ofthe batterycabinets.
UPS
Cabinet
Battery
Cabinet
Air Vents
UPS CabinetBattery Cabinet
Stacked Cabinets Side-by-Side Cabinets
Figure 3. Cabinet Setup
3. Verify the circuit breaker on all battery cabinets is inthe
OFF (O) position (see Figure 4).
4. Plug the battery output connector on the battery cable into the
external battery connector on the UPS. All battery connectors
are polarized to prevent incorrect connection.
5. If additional battery cabinets are to be used, plug the battery
output connector of the second cabinet into the battery input
connector of the first battery cabinet. Follow this procedure for
each additional battery cabinet.
6. Remove the breaker tie or clamp from the circuit breaker on all
battery cabinets.
7. Switch the circuit breaker on all battery cabinets to the ON (
)
position.
8. If your UPS is a 120V unit, see the following section, “UPS
Startup for 120V Models.” If your UPS is a 208V-240V unit,
skip to “UPS Startup for 208V-240V Models” on page 32.
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 69 70

Comments to this Manuals

No comments