7-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation
164201396 REV A 071103
7.4 O perating Modes
7.4.1 “ON LINE” Mode (INVERTER MODE)
The ON-LINE Mode is the UPS Operating Mode in which the load is supplied through
the RECTIFIER and INVERTER. LED indicators are illuminated when shown shaded:
LED’s green
when shown
shaded
Using the control panel (see Figure 7–2) the UPS can easily be transferred to the ON-
LINE mode. The ON-LINE mode provides the highest degree of protection, especially in
the event of a supply disturbance or failure. This operating mode is always
recommended if the critical loads (computer systems) will not tolerate any interruption of
the supply, even for a very short time. In the unlikely event of an inverter fault or
overload condition, the UPS will transfer the load automatically and without interruption
to the static bypass-utility supply.
7.4.2 “OFF LINE” Mode (BYPASS or ECONOMY MODE)
In the OFF-LINE mode, the load is supplied from the utility supply through the bypass.
Using the control panel (see Figure 7–2), the UPS may be easily transferred to “Bypass
Mode”.
LED’s green
when shown
shaded
When the UPS is operating in “Bypass Mode”, the efficiency of the system is higher. In
the event of a utility supply failure the load will automatically be transferred from utility to
LINE 2 BYPASS
BATTERY
LINE 1 INV.
LINE 2 BYPASS
BATTERY
LINE 1 INV.