Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 2-5
164201396 REV A 071103
2.
Remove Customer Interface conduit landing plate from the UPS cabinet. Drill or
punch conduit holes for interface wiring.
3. Open UPS cabinet front door and remove the front safety shield panel to gain access
to the wire way to bring wires from the conduit landing panel at the bottom rear of the
cabinet.
4.
Locate required connection points by referring to Figure A–1 in Appendix A.
5.
Refer to Appendix A of this manual for wiring and termination requirements.
6.
Reinstall Customer Interface conduit landing plate.
7. Install conduit and wiring.
8. When wiring is complete, secure UPS by reinstalling all panels removed in previous
steps.
2.3 Battery Cabinet Installation
The Powerware 9335 has no batteries within the UPS cabinet. An external battery
cabinet with appropriate batteries installed is required for proper system operation.
See installation instruction provided with the battery cabinet for proper installation of that
portion of the system.
2.4 Initial Startup
Startup and operational checks should be performed only by authorized service
personnel. Contact service in advance (usually a two week notice is required) to reserve
a preferred startup date.
2.5 Completing the Installation Checklist
The final step in installing your UPS system is completing the following Installation
Checklist. This checklist ensures that you have completely installed all hardware,
cables, and other equipment. Completing all items listed on the checklist will ensure a
smooth installation. You should make a copy of the Installation Checklist before filling it
out, and retain the original.
After your installation is complete, a service representative will be able to verify the
operation of your UPS system and commission it to support your critical load. The
service representative cannot perform any installation tasks other than verifying software
and operating setup parameters. Service personnel may request a copy of the
WARNING:
It is very important to ensure that a proper protective device is installed
between the battery system and the UPS DC input terminals. See Tables A
and B in Appendix A for proper wire and protective device sizing.