External Bypass Switch Installation
40
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
60 Hz 120 Vac Input - 120 Vac Output
Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch
Table 17. Minimum Recommended Circuit Breakers for 120 Vac
Charger 4.3 kVA 5.3 kVA 7kVA
Standard 40 50 70
10A 45 60 70
20A 50 60 70