External Bypass Switch Installation
37
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.
Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch
Table 14. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac
208 Vac 240 Vac
Charger 500 VA –1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 500 VA –1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
Standard 15 15 15 20 15 15 15 15
15A 15 20 25 30 15 20 20 25