Section 200: Startup
This section provides step-by-step instructions on starting your FERRUPS. We’ll explain how to turn on DC and
AC power and how to prepare the UPS to support your equipment.
201 Storing Your FERRUPS
If you do not plan to use your FERRUPS right away, you must store it between 20 and +40 Celsius ( 4 to
+104 Fahrenheit). If you remove the batteries and store them separately, you can store the UPS itself at 20 to
+60 C ( 4 to +140 F).
Keep batteries in storage fully charged. Recharge the batteries every 90-120 days.
Batteries will have a longer shelf life if you store them below 77 F (25 C).
202 Startup: FE and QFE 500VA to 3.1KVA
Make sure the temperature is 0 to 40 Celsius (32 to 104 Fahrenheit). The relative humidity must be 0-95%
without condensation. The air must be free of dust, chemicals that corrode, or other contaminants, and the air
must be free to move around FERRUPS.
Back View
1.8-3.1 kVA
1.15 and 1.4 kVA
500 VA-850 VA
1 = On/Off Switch 2 = Output Receptacles (for your equipment)
3 = RS232 Communication Port 4 = Alarm Silence Switch