Front Panel Menus
42
Powerware
®
5140 User’s Guide www.powerware.com
Set Voltage
Use the Set Voltage option to configure the UPS utility voltage. Use
and to scroll through the values. An asterisk (*) shows the
current configuration.
Select the appropriate utility voltage range (use Table 1 to help select
theappropriatevoltage):
200V
208V
220V
230V
240V
208/230V Auto-sensing
230V Extended (-35% to +20%)
Table 1. Nominal Input Voltage Ranges
NominalInput
Voltage (Vac)
NormalInput
Voltage Range
Extended Input
Voltage Range
200V Nominal +20%/–17% 166-240V
208V Nominal ±20% 166-248V
220V Nominal ±20% 176-264V
230V Nominal ±20% 184-276V 166-288V
240V Nominal ±20% 192-288V
Set Site Fault
Use the Set Site Fault option to enable or disable the site wiring fault
alarm. The default is disabled. Enable the alarm for installations where a
grounded-neutral electrical system is in place (see “Site Fault Wiring”
on page 57 for more information).
Set Sleep Mode
Use the Sleep Mode feature to control loads that use less than 10% of the
current when the UPS is on battery. The default is disabled.
Enable this option if you do not want a load less than 10%of the current
to be protected by battery power. This feature conserves battery power
by shutting down less critical loads.